Electrical transformer with cooling fins, bushings, and gauges for power distribution systems.
Electrical transformer with cooling fins, bushings, and gauges for power distribution systems.

10kV Oil-Immersed Three-Phase Double-Winding On-Load Voltage Regulating Distribution Transformer

FOB
MOQ:
1
Shipping:
Air freight, land freight, sea freight
Product details
FAQ
Essential details
MOQ:1
Shipping:Air freight, land freight, sea freight
Product Introduction
10 kV oil-immersed three-phase double-winding on-load voltage regulating distribution
transformer, with a capacity range of 200 to 2,500 kVA. Voltage ratio and tapping range
are configured to project requirements; vector group Dyn11 or Yyn0. Manufactured in
accordance with IEC 60076 and applicable GB standards.
  
Overview
1. Good economic performance. No-load current is reduced by 60%-80% on average, and no-load
loss by 25%-35% on average.
2. Long service life. The transformer tank adopts a fully sealed structure. The tank body
and the corrugated-fin wall can be joined by bolts or welding, so the insulating oil
does not come into contact with air, which extends service life.
3. High operational reliability. Sealing components on the tank have been improved in both
design and process quality to ensure seal integrity.
4. Small footprint. The corrugated-plate radiator expands and contracts with oil
temperature and takes the place of a separate oil conservator. The corrugated-plate tank
also gives a clean appearance and a small footprint.

ON-LOAD TAP CHANGING
The on-load tap changer allows the voltage ratio to be adjusted while the transformer is
energised and carrying load. Tapping ranges of ±4×2.5% are available. This suits
distribution networks where the supply voltage varies during the day and the transformer
cannot be switched out for adjustment.

Outline Installation Dimensions


Applications
Suited to distribution networks and substations, industrial plants and commercial sites.
Configuration can be adjusted to project requirements, including voltage ratio, tapping
range, vector group and loss level.

Request a Quotation
Send us the rated capacity, voltage ratio, tapping range, vector group and destination
country, and we will confirm the recommended configuration, price and lead time.